Application of the EL CID Test with
Circulating Currents in Stator Windings
John Sutton, David Bertenshaw
Summary
EL CID tests are carried out to
determine the integrity of the inter-lamination insulation in large stator
cores. This parameter is critical as not only does degradation result in
increased losses, but the resultant heating can damage conductor insulation and
in severe cases melt the stator iron.
It is generally assumed that
currents do not flow in the stator winding during an EL CID test. This
assumption is based on the expectation that an EL CID excitation generates a
truly circumferential flux around the stator core so that no magnetic flux links
the stator winding and no currents are induced in it. However occasionally test
results on generators have produced large fluctuations in Phase and (to a lesser
extent) Quad values, for which there has been no satisfactory answer.
Recently EL CID tests were carried
out on a large hydro-generator with a split stator core, both before and after
the stator windings (9 parallels) had been fitted. With the windings in place
the Phase readings varied greatly, even becoming negative, but had been
acceptably stable without the winding. It was discovered that circulating
currents were flowing in the parallel circuits, both by direct measurement and
deduction from the results and the winding diagram. Once these currents were
taken account of, the test results were normalised and showed the machine’s true
condition.
An earlier test on a
turbo-generator had similarly produced very variable and also negative Phase
readings when tested with a very asymmetric excitation winding. The problem had
originally been resolved by using the correct axial excitation. Whilst there had
been supposition that currents were flowing in the windings, there were no
parallels. However with a revised analysis, circulating currents were clearly
flowing between the earth bonded phases.
From these results, test analysis
methods that allow correct interpretation are given, showing that the standard
approach can continue to be used with the new understanding.
John Sutton, Consultant
The Willows,
Mid Holmwood Lane,
Mid Holmwood
Dorking, Surrey. RH5 4HA.
UK
David Bertenshaw, UK Operations
Director
ADWEL International Ltd
Park House
Greenhill Crescent
Watford Business Park
Watford, Herts. WD18 8PH
UK
tel: +44 1923 254433, fax: +44 1923
218278,
email:
dbertenshaw@adwel.co.uk web site: www.adwel.com