THE MONITORING SYSTEMS FOR ROTATING MACHINES PD-ACTIVITY MEASUREMENTS

 

Y.P. Aksenov “DIACS”, (Moscow, Russia)

G.Noe, “Comelmar” (Italy); I.Arces, “ENI” (Italy)

 

Abstract: The report contains the results of inspection before maintenance’s revealed defect data in stator and rotor insulation, and on-line sparking and PD location by means of measuring of electrical PD-pulses on turbo generator tank. The double-coordinate (angle length) location technology of pinpointing is used to coordinate: slot number – length the rod. Features measuring sensors collation, producing double-coordinate diagnostics, with the signal from the coupler capacitor of monitoring system, install on generator line leads.

 

 

 

 

DIACS                                         

Kitaigorodsky pr.7

109074 Moscow

Russia

Phone/fax

(095) 315 29 54

E-mail:

diacsnew@mtu-net.ru

Yu.P.Aksenov's home:

Leningradsky pr., 75 "A", ap.42

125057, Moscow, Russia

Phone/fax (095) 157 57 93